This report describes new full-scale compartment fire experiments, which include local measurements of temperature, heat flux and species composition, and global measurements of heat release rate and mass burning rate. The measurements are unique to the compartment fire literature. By design, the experiments provided a comprehensive and quantitative assessment of major and minor carbonaceous gaseous species and soot at two locations in the upper layer of fire in a full scale ISO 9705 room.
This report describes new full-scale compartment fire experiments, which include local measurements of temperature, heat flux and species composition,...
This report presents the methodology for and results from a series of room-scale fire tests to produce data on the yields of toxic products in both pre-flashover and post-flashover fires. The combustibles examined were: a sofa made of upholstered cushions on a steel frame, particleboard bookcases with a laminated finish, polyvinyl chloride sheet, and household electric cable. They were burned in a room with a long adjacent corridor. The yields of CO2, CO, HCl, HCN, and carbonaceous soot were determined. Other toxicants (e.g., NO2, formaldehyde and acrolein) were not found; concentrations...
This report presents the methodology for and results from a series of room-scale fire tests to produce data on the yields of toxic products in both pr...